Monobloc VS-ECO

Home › Products › Monobloc VS-ECO

Monobloc VS-ECO

Plate heat exchanger > 85% · EC fan
Air handling unit

6 models from 700 to 3,200 m³/h

6 models for airflows from 700 to 3,200 m³/h, fitted with a high-efficiency plate heat exchanger (over 85%) and an EC fan without controls.

Drawings also available in REVIT format.

Technical data

Specifications by model

700 m³/h

ECO 700

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air700 m³/h780 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A
Extract air700 m³/h760 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 700 BP1385 × 725 × 1620 mm200kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

1200 m³/h

ECO 1200

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air1200 m³/h540 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A
Extract air1200 m³/h510 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 1200 BP1640 × 725 × 1910 mm260kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

1600 m³/h

ECO 1600

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air1600 m³/h640 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A
Extract air1600 m³/h610 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 1600 BP1690 × 925 × 1910 mm310kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

2000 m³/h

ECO 2000

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air2000 m³/h450 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A
Extract air2000 m³/h430 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 2000 BP1690 × 1025 × 1910 mm330kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

2500 m³/h

ECO 2500

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air2500 m³/h650 Pa1.05 kW1.6 A3× 400 V3LNPE 3×16A
Extract air2500 m³/h620 Pa1.05 kW1.6 A3× 400 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 2500 BP1890 × 1125 × 2040 mm410kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

3200 m³/h

ECO 3200

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air3200 m³/h890 Pa1.8 kW2.8 A3× 400 V3LNPE 3×16A
Extract air3200 m³/h510 Pa1.8 kW2.8 A3× 400 V3LNPE 3×16A

F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
ECO 3200 BP1940 × 1225 × 2040 mm470kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

Downloads

VS-ECO data sheets

Data sheets for the 6 models (PDF).

Which VS-ECO model for your project?

From 700 to 3,200 m³/h, high-efficiency plate heat recovery. Request your quote.