Monobloc VS-ECO
6 models from 700 to 3,200 m³/h
6 models for airflows from 700 to 3,200 m³/h, fitted with a high-efficiency plate heat exchanger (over 85%) and an EC fan without controls.
Drawings also available in REVIT format.
Specifications by model
ECO 700
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 700 m³/h | 780 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 700 m³/h | 760 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 700 BP | 1385 × 725 × 1620 mm | 200kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
ECO 1200
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 1200 m³/h | 540 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 1200 m³/h | 510 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 1200 BP | 1640 × 725 × 1910 mm | 260kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
ECO 1600
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 1600 m³/h | 640 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 1600 m³/h | 610 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 1600 BP | 1690 × 925 × 1910 mm | 310kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
ECO 2000
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 2000 m³/h | 450 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 2000 m³/h | 430 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 2000 BP | 1690 × 1025 × 1910 mm | 330kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
ECO 2500
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 2500 m³/h | 650 Pa | 1.05 kW | 1.6 A | 3× 400 V | 3LNPE 3×16A |
| Extract air | 2500 m³/h | 620 Pa | 1.05 kW | 1.6 A | 3× 400 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 2500 BP | 1890 × 1125 × 2040 mm | 410kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
ECO 3200
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 3200 m³/h | 890 Pa | 1.8 kW | 2.8 A | 3× 400 V | 3LNPE 3×16A |
| Extract air | 3200 m³/h | 510 Pa | 1.8 kW | 2.8 A | 3× 400 V | 3LNPE 3×16A |
F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| ECO 3200 BP | 1940 × 1225 × 2040 mm | 470kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
VS-ECO data sheets
Data sheets for the 6 models (PDF).
Which VS-ECO model for your project?
From 700 to 3,200 m³/h, high-efficiency plate heat recovery. Request your quote.