Home › Products › Monobloc VS-MEG

Monobloc VS-MEG

24 models · integrated Climatix controls
Air conditioning and ventilation

A complete range, controlled and certified

DEPAIR SA has developed a range of 24 air conditioning and ventilation unit models for airflows from 500 to 3,200 m³/h.

These models are fitted with high-efficiency plate heat exchangers (approx. 85%), EC fans and complete controls with data transmission over Modbus TCP or BACnet IP (Climatix as standard). Superior quality components for optimal efficiency and long-term reliability.

Our units are identical to those of the VS-SP range, tested and TÜV-certified to standard EN 1886, rated T2/TB1. Models for higher airflows can be developed on request. Drawings available in REVIT format.

Optional:

Heating and cooling coil management · fire damper management with or without the EasyBus system · K-factor for the fans.

Configuration types

Four layouts: S · H · V · V1

VS-MEG layout type S: supply (AP), extract (AE), fresh (AN) and exhaust (AV) air paths crossing inside the unit
Type S
VS-MEG layout type H: supply (AP), extract (AE), fresh (AN) and exhaust (AV) air passing straight through the unit
Type H
VS-MEG layout type V: extract (AE) and supply (AP) air connected upwards
Type V
VS-MEG layout type V1: fresh (AN) and exhaust (AV) air connected on top, extract (AE) and supply (AP) air on the sides
Type V1
Technical data

Specifications by airflow

The technical data below is given according to the unit airflow [m³/h].

700 m³/h

MEG 700

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air700 m³/h780 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A
Extract air700 m³/h760 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements. Minimum airflow 500 m³/h through EC fan modulation.

TypeH × W × LengthWeight
MEG 700 S1450 × 735 × 1670 mm240 kg
MEG 700 H1240 × 735 × 2290 mm300 kg
MEG 700 V1500 × 735 × 1700 mm220 kg
MEG 700 V11200 × 735 × 2390 mm340 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

1,200 m³/h

MEG 1200

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air1,200 m³/h540 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A
Extract air1,200 m³/h510 Pa0.5 kW2.3 A1× 230 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
MEG 1200 S1650 × 735 × 1800 mm280 kg
MEG 1200 H1240 × 735 × 2450 mm330 kg
MEG 1200 V1700 × 735 × 1790 mm240 kg
MEG 1200 V11250 × 735 × 2520 mm420 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

1,600 m³/h

MEG 1600

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air1,600 m³/h640 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A
Extract air1,600 m³/h610 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
MEG 1600 S1650 × 935 × 1800 mm320 kg
MEG 1600 H1240 × 935 × 2470 mm350 kg
MEG 1600 V1700 × 935 × 1790 mm280 kg
MEG 1600 V11250 × 935 × 2520 mm420 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

2,000 m³/h

MEG 2000

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air2,000 m³/h450 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A
Extract air2,000 m³/h430 Pa0.75 kW3.3 A1× 230 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
MEG 2000 S1750 × 935 × 1900 mm350 kg
MEG 2000 H1240 × 935 × 2610 mm370 kg
MEG 2000 V1800 × 935 × 1930 mm310 kg
MEG 2000 V11310 × 935 × 2630 mm440 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

2,500 m³/h

MEG 2500

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air2,500 m³/h650 Pa1.05 kW1.6 A3× 400 V3LNPE 3×16A
Extract air2,500 m³/h620 Pa1.05 kW1.6 A3× 400 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
MEG 2500 S1790 × 1135 × 1900 mm410 kg
MEG 2500 H1330 × 1135 × 2645 mm440 kg
MEG 2500 V1850 × 1135 × 2000 mm360 kg
MEG 2500 V11350 × 1135 × 2770 mm520 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

3,200 m³/h

MEG 3200

AirflowMax. external pressure*Motor powerCurrentVoltagePower supply
Supply air3,200 m³/h890 Pa1.8 kW2.8 A3× 400 V3LNPE 3×16A
Extract air3,200 m³/h860 Pa1.8 kW2.8 A3× 400 V3LNPE 3×16A

ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.

TypeH × W × LengthWeight
MEG 3200 S1870 × 1235 × 1950 mm490 kg
MEG 3200 H1360 × 1235 × 2840 mm540 kg
MEG 3200 V2050 × 1235 × 2100 mm460 kg
MEG 3200 V11450 × 1235 × 2940 mm640 kg

Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).

Downloads

VS-MEG data sheets & drawings

Documents by model and configuration (48 PDFs).

Need a controlled air handling unit?