Monobloc VS-MEG
A complete range, controlled and certified
DEPAIR SA has developed a range of 24 air conditioning and ventilation unit models for airflows from 700 to 3,200 m³/h.
These models are fitted with high-efficiency plate heat exchangers (approx. 85%), EC fans and complete controls with data transmission over Modbus TCP or BACnet IP (Climatix as standard). Superior quality components for optimal efficiency and long-term reliability.
Our units are identical to those of the VS-SP range, tested and TÜV-certified to standard EN 1886, rated T2/TB1. Models for higher airflows can be developed on request. Drawings available in REVIT format.
Heating and cooling coil management · fire damper management with or without the EasyBus system · K-factor for the fans.
Four layouts: S · H · V · V1




Specifications by airflow
The technical data below is given according to the unit airflow [m³/h].
MEG700
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 700 m³/h | 780 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 700 m³/h | 760 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 700 S | 1450 × 735 × 1670 mm | 240 kg |
| MEG 700 H | 1240 × 735 × 2290 mm | 300 kg |
| MEG 700 V | 1500 × 735 × 1700 mm | 220 kg |
| MEG 700 V1 | 1200 × 735 × 2390 mm | 340 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
MEG1200
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 1200 m³/h | 540 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 1200 m³/h | 510 Pa | 0.5 kW | 2.3 A | 1× 230 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 1200 S | 1650 × 735 × 1800 mm | 280 kg |
| MEG 1200 H | 1240 × 735 × 2450 mm | 330 kg |
| MEG 1200 V | 1700 × 735 × 1790 mm | 240 kg |
| MEG 1200 V1 | 1250 × 735 × 2520 mm | 420 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
MEG1600
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 1600 m³/h | 640 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 1600 m³/h | 610 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 1600 S | 1650 × 935 × 1800 mm | 320 kg |
| MEG 1600 H | 1240 × 935 × 2470 mm | 350 kg |
| MEG 1600 V | 1700 × 935 × 1790 mm | 280 kg |
| MEG 1600 V1 | 1250 × 935 × 2520 mm | 420 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
MEG2000
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 2000 m³/h | 450 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
| Extract air | 2000 m³/h | 430 Pa | 0.75 kW | 3.3 A | 1× 230 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 2000 S | 1750 × 935 × 1900 mm | 350 kg |
| MEG 2000 H | 1240 × 935 × 2610 mm | 370 kg |
| MEG 2000 V | 1800 × 935 × 1930 mm | 310 kg |
| MEG 2000 V1 | 1310 × 935 × 2630 mm | 440 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
MEG2500
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 2500 m³/h | 650 Pa | 1.05 kW | 1.6 A | 3× 400 V | 3LNPE 3×16A |
| Extract air | 2500 m³/h | 620 Pa | 1.05 kW | 1.6 A | 3× 400 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 2500 S | 1790 × 1135 × 1900 mm | 410 kg |
| MEG 2500 H | 1330 × 1135 × 2645 mm | 440 kg |
| MEG 2500 V | 1850 × 1135 × 2000 mm | 360 kg |
| MEG 2500 V1 | 1350 × 1135 × 2770 mm | 520 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
MEG3200
| Airflow | Max. external pressure* | Motor power | Current | Voltage | Power supply | |
|---|---|---|---|---|---|---|
| Supply air | 3200 m³/h | 890 Pa | 1.8 kW | 2.8 A | 3× 400 V | 3LNPE 3×16A |
| Extract air | 3200 m³/h | 860 Pa | 1.8 kW | 2.8 A | 3× 400 V | 3LNPE 3×16A |
ISO ePM1 60% / F7 filter. *Values at 400 m (ρ = 1.15 kg/m³). Low-voltage conductor cross-sections to be sized in accordance with the local energy supplier’s requirements.
| Type | H × W × Length | Weight |
|---|---|---|
| MEG 3200 S | 1870 × 1235 × 1950 mm | 490 kg |
| MEG 3200 H | 1360 × 1235 × 2840 mm | 540 kg |
| MEG 3200 V | 2050 × 1235 × 2100 mm | 460 kg |
| MEG 3200 V1 | 1450 × 1235 × 2940 mm | 640 kg |
Options: surface-mounted heating coil · rooftop installation (side inlets and outlets).
VS-MEG data sheets & drawings
Documents by model and configuration (48 PDFs).
| Model | Config. S | Config. H | Config. V | Config. V1 |
|---|---|---|---|---|
| MEG 700 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
| MEG 1200 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
| MEG 1600 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
| MEG 2000 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
| MEG 2500 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
| MEG 3200 | Technical · Drawing | Technical · Drawing | Technical · Drawing | Technical · Drawing |
Need a controlled air handling unit?
Climatix controls, Modbus TCP / BACnet IP, TÜV EN 1886 certification. Request your VS-MEG quote.
Request a quote